ECOFLOW & MULTIFLOW

Principle and Operation

With this type of recovery system, composed of 2 interconnected heat exchangers with a separate circuit, the heat transfer takes place through glycolised water which is continuously passed through the extract and supply air by use of a pump. The medium absorbs the energy from the extract air and transfers it to the fresh air. For Multiflow, multiple recuperators are combined per air flow.

  •  

    Ecoflow
  •  

    Ecoflow in CAIRplus

Features and Focal Points

  • Power can be controlled by a mixing valve (in case of no mixing valve: control by switching pump on/off)
  • 100% guarantee of separated air flows and therefore especially suitable if no leakages between supply and extraction are allowed (no risk of contamination)
  • Connection must always be carried out in countercurrent (water inlet side to air inlet side)
  • Compact and flexible solution
  • Several extraction units can be connected to 1 / more supply unit(s)
  • Through the interposition of plate heat exchangers (water/water) these recuperators also enable heating and cooling
  • Simple temperature control by 3-way valve
  • ATTENTION: in conformity with Erp Ecodesign 2016-17. For Erp 2018, many rows and low passage velocities are required
Contact Us

DencoHappel GmbH

Südstraße 48
44625 Herne
Germany
+49 2325 468-00
+49 2325 468-222
DH Points
  • Category IIa according to EN308
  • Superposition, juxtaposition, mounted separately or in a line
  • Max. air flow rate 90,000 m³/h
  • Yields up to 63% or 67% according to EN308
  • Integration in CAIRplus & CAIRfricostar
  • Applications: pharmaceutical industry, cleanrooms, hospitals